Drawing Impedance Diagrams

Not what you're looking for?

Ask Custom Question

A 415 V, 3-phase generator supplying a 3-phase 415/110 V transformer. Draw the individual and combined impedance diagrams to a base of 10 kVA. Determine the system fault kVA and the fault currents at the 415 V and 110 V busbars for short circuit faults on the transformer input or output terminals. Work in p.u. values of impedances.

Purchase this Solution

Solution Summary

The expert examines drawing impedance diagrams for circuit faults. The values of impedances are determined.

Solution Preview

A 16 kW, 415 V, 0.8 pf 3-phase generator (X = 20%) is supplying a 5 kVA, 3-phase 415/110 V transformer (X = 8%). Draw the individual and combined impedance diagrams to a base of 10 kVA. Determine the system fault kVA and the fault currents at the 415 V and 110 V busbars for short circuit faults on the transformer input or output terminals. Work in p.u. values of impedances.
Solution:
G 16 kW, 415 V, 0.8 pf, 3 phase (X = 20%)

415 V Bus

...

Purchase this Solution